Overview

The logical input card for a function or control slot has 8 control inputs which may receive signals from other systems in order to trigger a desired reaction of EST ENT VES system. Inputs of an EST-xLogIN-8c/f card offer two modes of operation: contact mode (short / open contact) and monitor mode in which in addition to contact mode function, short circuit and opening of the cables connected to the card are detected.

Technical specifications

Electrical
Operating voltage
12 V, Internal from the Control Unit
Current consumption
10 mA at 48 V
Physical
Physical dimensions
70 x 215 x 25 mm (W x H x D)
Type of connector 16-pin screw terminal type PHOENIX, 3.5 mm
Accessories Connector with screw terminals 16 pins, the distance between the partitions of 3.5 mm
Environmental
Operating temperature
0 to +60°C
Storage temperature
-20 to +70°C
Relative humidity
15 to 80% noncondensing (Operating)
5 to 95% noncondensing (Storage)
Regulatory
Standards
EN54-16
Input
Number of logic inputs 8
Voltage source 12 V
Type of control logic NO / NC
Resistance value interpreted as the opening of the line RL>20k
Resistance value interpreted as a contact close RL<5k
Resistance value interpreted as a contact open RK>10k