EST-XLOGIN-8C
Logical inputs card (control slot), 8 inputs
Alternative products
Related products
At a glance
Overview
The logical input card for a function or control slot has 8 control inputs which may receive signals from other systems in order to trigger a desired reaction of EST ENT VES system. Inputs of an EST-xLogIN-8c/f card offer two modes of operation: contact mode (short / open contact) and monitor mode in which in addition to contact mode function, short circuit and opening of the cables connected to the card are detected.
Technical specifications
| Electrical | ||
|---|---|---|
| Operating voltage |
12 V, Internal from the Control Unit
|
|
| Current consumption |
10 mA at 48 V
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
70 x 215 x 25 mm (W x H x D)
|
|
| Type of connector | 16-pin screw terminal type PHOENIX, 3.5 mm | |
| Accessories | Connector with screw terminals 16 pins, the distance between the partitions of 3.5 mm | |
| Environmental | ||
|---|---|---|
| Operating temperature |
0 to +60°C
|
|
| Storage temperature |
-20 to +70°C
|
|
| Relative humidity |
15 to 80% noncondensing (Operating)
5 to 95% noncondensing (Storage)
|
|
| Regulatory | ||
|---|---|---|
| Standards |
EN54-16
|
|
| Input | ||
|---|---|---|
| Number of logic inputs | 8 | |
| Voltage source | 12 V | |
| Type of control logic | NO / NC | |
| Resistance value interpreted as the opening of the line | RL>20k | |
| Resistance value interpreted as a contact close | RL<5k | |
| Resistance value interpreted as a contact open | RK>10k | |