Skip to main content

GST104A

Conventional Fire Alarm Control Panel
  • 4 Detection zones
  • Each zone can support up to 15 conventional detectors or 32 manual call points, to a combined total of 32 devices.
  • Short and open circuit reporting of detection zones, sounder and alarm outputs
  • Space provided inside the CIE cabinet for 2 SLA batteries for standby support
  • Easy enable/disable operation for zones, sounder and alarm outputs
View all

At a glance

General

The GST104A is compatible with GST conventional detectors, manual call points and sounders. The panel is easy to install and operate. Control functions are enabled by key switch whilst programming functions are enabled by key switch in combination with an internal switch.

Installation

The GST104A may be wall or flush-mounted.

Details

  • 4 Detection zones
  • Each zone can support up to 15 conventional detectors or 32 manual call points, to a combined total of 32 devices.
  • Short and open circuit reporting of detection zones, sounder and alarm outputs
  • Space provided inside the CIE cabinet for 2 SLA batteries for standby support
  • Easy enable/disable operation for zones, sounder and alarm outputs
  • Alarm test function selectable with or without sounder notification
  • Programmable output for linking zones and sounder outputs, alert or evacuate tone, with or without delay
  • Day/Night mode selectable
  • Silence/Reset/Test modes selectable to local requirements
  • Three access levels configurable via key control
  • Reserved multi zone repeater interface for fire alarm indications

Technical specifications

General
Connectivity
Hardwired repeater
Maximum system capacity (device count)
up to 128
Cable rating 0.5 mm (max)
Electrical
Power supply type
220/230 VAC
Power consumption
+10/-15%, 50 / 60 Hz
Zone
Maximum zone capacity
up to 4
Quantity of devices per zone
15 detectors / 32 MCPs
Cable rating
1.0 to 1.5 mm², 1000 m (max.)
End-of-line Active
Passive (4.7 kΩ, ½W)
Input
Input quantity
4
Input type and rating
Unsupervised NO, Cable type: 0.5 mm² (min.)
Programmable
No
Output
Output type and rating
Cable type: 1.0 to 1.5 mm², 1000 m (max.)
Fire alarm signalling
1, 300 mA @ 24 VDC or NO/NC
Fault signalling
1, NO/COM/NC, 1 A @ 24 VDC
Notification
4, 300 mA @ 24 VDC or NO/NC
Auxilliary power
<500 mA @ 24 VDC (18 to 26 VDC)
Programmable
Yes
Termination
4.7 kΩ, 0.5 W
Standby battery
Capacity
7 Ah
Batteries supported in housing
2 x 12 VDC
Physical
Form factor
Small
Physical dimensions
380 x 320 x 103 mm (W x H x D)
Colour
Black
Mounting type
Surface mount
Wall mount
Environmental
Vandal proof
No
Operating temperature
0 to 40°C
Relative humidity
0 to 95% noncondensing
Environment
Indoor
IP rating
IP30
Regulatory
Compliancy
CE
Certification
EN54-2
EN54-4
Standards
LPCB