WFA20210N
Fire retardant cable 2 X 1 mm.sq., PH120, (200 m Reel)
- Stranded copper wire conductors
- Special silicon rubber mix insulation
- Halogen free sheath
- EN 50200 - Class PH 120 rating
Related products
At a glance
General
The WFA20210N is a single pair, twisted cable with screen and special silicon rubber mix insulation.
It is ideal for use in fire detection systems where circuit integrity is important.
The WFA20210N is sold in 200m lengths.
It is ideal for use in fire detection systems where circuit integrity is important.
The WFA20210N is sold in 200m lengths.
Construction
It features stranded copper wire conductors and the collective screen consist of aluminum/polyester tape.
Standard References
The WFA20210N is PH120 rated according to EN 50200.
Additionally complies with:
- BS EN 50267-2-1
- BS 7655 1.1
- BS 7655 6.1
- EC 60331-21
Additionally complies with:
- BS EN 50267-2-1
- BS 7655 1.1
- BS 7655 6.1
- EC 60331-21
Details
- Stranded copper wire conductors
- Special silicon rubber mix insulation
- Halogen free sheath
- EN 50200 - Class PH 120 rating
Technical specifications
| General | ||
|---|---|---|
| Minimum insulation resistance |
200 Mohm/km
|
|
| Test voltage |
2000 V
|
|
| Conductor | ||
|---|---|---|
| Cross section |
1.0 mm²
|
|
| No. of conductors |
2 cores
|
|
| Colour of conductors |
Brown and Blue
|
|
| Resistance |
19.9 ohm/km at +20°C
|
|
| Capacitance |
150 nF/km at 20°C
|
|
| Inductance |
1 mH/km
|
|
| Physical | ||
|---|---|---|
| Outer diameter |
6.3 mm
|
|
| Net weight |
59 kg/km
|
|
| Colour |
Red
|
|
| Minimum bending radius | 8 x Overall diameter | |
| Environmental | ||
|---|---|---|
| Operating temperature |
-40 to +180°C
-5 to +50°C, installation
|
|
| Fire Retardant rating |
120 min
|
|
| Regulatory | ||
|---|---|---|
| Standards |
EN 50200 (Class PH 120)
|
|
Downloads
All downloadsDatasheet
Certificates
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.