Skip to main content

GST200N-1

GST200N Addressable 1 Loop Panel (English)
  • Max. 30 zones, each zone has its own alarm and fault/disable indicator and a label
  • Single loop panel capacity 235 addressable devices. Can be extended to 2 loops by using an additional loop card (LC200).
  • Compatible with GST intelligent and digital products
  • 8 lines x 18 characters LCD screen
  • 15 LEDs to display important information
View all

At a glance

Product overview

GST200N Intelligent Fire Alarm Control Panels are designed in comply with EN54-2 and EN54-4 standard with qualities of simple installation, operation, and easy maintenance. 1-2 loop addressable panel is suitable for small buildings like office, restaurant, store, shop, etc.

Details

  • Max. 30 zones, each zone has its own alarm and fault/disable indicator and a label
  • Single loop panel capacity 235 addressable devices. Can be extended to 2 loops by using an additional loop card (LC200).
  • Compatible with GST intelligent and digital products
  • 8 lines x 18 characters LCD screen
  • 15 LEDs to display important information
  • Non-Volatile memory ensures no loss of data even if power supply is accidentally removed
  • Wide range power supply
  • Sounder strobe output provides 0.5 A / 24 V load, compatible with GST conventional sounders
  • RS232 interface enables communication with PC, advanced user friendly programming software including ‘Fuzzy logic'
  • RS485 (max 32 panels w/ card) or CAN (max 240 panels w/ card) interface enables networking, built-in RS485 repeater output (max. 10 repeaters)
  • Multiple language options (separate SKUs)
  • Optional panel printer and GMC graphic station
  • PAS and Acknowledge Function, Dirty Detector Reporting, Walk Test Function

Technical specifications

Electrical
Power consumption
Standby: 21 Ah / 24 VDC
Operating voltage
100 to 240 VAC, 50/60 Hz
Current consumption
1.5 A
Loop
Maximum loop capacity
1
Quantity of devices per loop
235
Cable rating
Min. 1.0 mm2, ideally 1.5 mm2, 1500 m
Zone
Maximum zone capacity
up to 30
Output
Output quantity
3
Output type and rating
Min. 1.5 mm2, ideally 2.5 mm2
Fire alarm signalling
500 mA / 24 VDC / NO-NC-Active
Fault signalling
NO / NC
Termination
4k7 ohm
Physical
Form factor
Large
Physical dimensions
580 x 420 x 202 mm (H x W x D)
Mounting type
Surface mount
Environmental
Operating temperature
0 to +40°C
Relative humidity
≤95% noncondensing
IP rating
IP30
Regulatory
Certification
CE
LPCB
Standards
EN54-2
EN54-4