Skip to main content

DI-9204E

Innovation Intelligent DI-9000E Series Addressable Manual Call Point
  • Non-break activation with easy reset using a special key
  • Advanced digital communication
  • Electronic addressing
  • Easy installation with plugin connector
  • Easy test function
View all

At a glance

General

The DI-9204E is in intelligent digital manual call point operating on the latest digital loop protocol. It is compatible with the GST200N and GST-IFP4E intelligent fire alarm control panels where it allows a direct user interface with the fire alarm system for manual alarm reporting.
The DI-9204E is a semi-flush mount type MCP. A back box is supplied with the MCP for surface mounting.

Operation

An alarm is reported by pressing the resettable element. The alarm is confirmed by the DI-9204E by an illuminated LED. The alarm is signalled automatically to the CIE. To reset a special key is supplied with the unit.

Installation

The DI-9204E is simply connected by two wires to any compatible fire alarm zone monitor where it gets its power and reports events using the same 2 wires. The provided reset key is also used to unlock the MCP.
The DI-9204E is suitable for public places where accidental activation can be avoided by using an optional protection flip cover (D-92FC). For outdoor applications a weatherproof enclosure (D-92WPB) is additionally available.

Details

  • Non-break activation with easy reset using a special key
  • Advanced digital communication
  • Electronic addressing
  • Easy installation with plugin connector
  • Easy test function
  • Dual activation indication i.e. via LED and alarm flag on the face of the unit
  • Surface or semi flush mount
  • Protection hinged cover & outdoor mounting box available
  • Approved to the latest standards, LPCB marked

Technical specifications

General
Status indication
Red LED
Compatibility
GST DI-9000E series systems
Connectivity
2-wire loop
Addressing method
Electronic
Electrical
Power supply type
Loop powered
Operating voltage
16 to 28 VDC
24 VDC (typical)
Current consumption
0.6 mA (Standby)
≤1.8 mA (Alarm)
Cable specification
>1.0 mm²
No. of cable cores
2
Terminals
4
Detection
Detection principle
Microswitch
Coverage area
Subject to local codes
Zone length
CIE Specific
Isolation
Series resistance
470 Ω ½ W
Physical
Physical dimensions
87.1 x 87.1 x 58.5 mm (W x H x D)
Shipping weight
160 g
Colour
Red
Mounting type
Back box
Wall mount
Cable entries
3
Material (body)
ABS
Functional marking
House of Fire
Environmental
Vandal proof
No
Operating temperature
-10 to +55°C
Relative humidity
≤95% noncondensing
Environment
Indoor
IP rating
IP43
Regulatory
Compliancy
CE
REACH
RoHS
WEEE
Certification
CPR
Standards
EN54-11