Skip to main content

DC-9102E

DC9000 Series conventional optical smoke detector
  • Supports drift compensation to enable good environmental adaptability
  • Self-diagnostic
  • Local test activation with reed switch
  • Chamber contamination checking
  • All round LED visibility (360° viewing angle) avoids time spent on specific detector orientation
View all

Related products

At a glance

General

The DC-9102E is a photoelectric (optical) detector suitable for use in hotels, restaurants, office buildings, schools, banks, warehouses, libraries, computer rooms, switch rooms, etc.

Application

The detector supports installation on the GST DB-01 conventional detector base for standard applications, or the GST DB-01D diode base when head-out functionality to BS5839 standard is required. Detection sensitivities are programmable using the GST P-9910B device programmer.

Details

  • Supports drift compensation to enable good environmental adaptability
  • Self-diagnostic
  • Local test activation with reed switch
  • Chamber contamination checking
  • All round LED visibility (360° viewing angle) avoids time spent on specific detector orientation
  • Configurable polling LED support
  • Remote indicator output
  • Removable sensing chamber for for easy maintenance
  • 2 Programmable smoke sensitivity levels

Technical specifications

General
Status indication
Red LED
User interface
Via LED - polling, fault, contamination and alarm
Compatibility
GST100A Series conventional CIEs as well as GST I-9319 Zone Monitor
Reset voltage
<1 VDC
Reset time
>2 s
Alarm levels
2
Connectivity
Zone connection - 2-core (polarity sensitive), RI connection - 2-core (polarity sensitive)
Electrical
Operating voltage
16 VDC to 28 VDC (24 VDC typical)
Current consumption
<60 μA (Quiescent)
≤55 mA (Alarm)
Cable specification
>1.0 mm²
No. of cable cores
2
Terminals
4
Detection
Detection principle
Optical
Sensitivity
Programmable
Zone length
Panel dependent
Output
Remote alarm output
1
Physical
Physical dimensions
54.5 mm (including base) x 100 mm Ø
Net weight
±110 g
Colour
White
Mounting type
Ceiling mount
Material (body)
ABS
Environmental
Vandal proof
No
Operating temperature
-10 to +50°C (Class A1/A2)
-10 to +65°C (Class B)
Relative humidity
0 to 95% noncondensing
Environment
Indoor
IP rating
IP2x
Regulatory
Compliancy
CE
WEEE
Certification
EN54-7
Standards
LPCB