Skip to main content

FHSD8210-99

LaserSense HSSD2 High Sensitivity Smoke Detector - Minimum display version
  • High sensitivity provided by laser based forward light scatter for reliable early warning
  • Combined sampling pipe up to 200m in length (still air)
  • Unique ClassiFire® Perceptive Artificial Intelligence system that dynamically adjusts the detector’s operating parameters, allowing for day to day changes in the protected environment and dust separation system contamination
  • Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and elimination system
  • RS485 communications built in as standard for networking and remote communications
View all

At a glance

Description

LaserSense HSSD2 is designed to provide very high sensitivity smoke detection, ensuring the very earliest warning of incipient fire with minimum rate of nuisance alarms.

ClassiFire Perceptive Artificial Intelligence ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.

Upgradable volt-free Fire and Fault relay outputs are available for remote monitoring by local fire detection or BMS systems.

Typical Applications

• Data storage units
• Prison cells
• Plant rooms
• Air conditioning units
• Equipment racks
• Computer rooms
• Air duct protection
• Heritage property protection
• Critical equipment
• Anti-smoking enforcement
• Motor rooms

Options Available

• Addressable Protocol Interface Cards APIC™ available for Ziton protocol
• Command Module available for central monitoring and display
• SenseNet compatible - up to 127 detectors per loop
• Remote Display units available
• Suitable for MatrixScan, a patented software system which provides virtual addressable location detection - e.g. 10 physical detectors would provide up to 45 unique addressable locations.

Details

  • High sensitivity provided by laser based forward light scatter for reliable early warning
  • Combined sampling pipe up to 200m in length (still air)
  • Unique ClassiFire® Perceptive Artificial Intelligence system that dynamically adjusts the detector’s operating parameters, allowing for day to day changes in the protected environment and dust separation system contamination
  • Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and elimination system
  • RS485 communications built in as standard for networking and remote communications

Technical specifications

Electrical
Operating voltage
21.6 to 26.4 VDC
Current consumption
450 mA at fan speed 8
Detection
Detection principle
Laser light scattering mass detection and particle evaluation
Particle sensitivity range
0.003μ to 10μ
Detection principle Laser light scattering mass detection and particle evaluation
Particle sensitivity range 0.003μ to 10μ
Measurement range (%Obs/m) 0.0015% to 25%
Alarm levels 4 (Aux, Pre-alarm, Alarm and Alarm 2)
Physical
Physical dimensions
427 x 372 x 95 mm (W x H x D)
Net weight
5.2 kg
Colour
Cream
Mounting type
Surface mount
Cable entries
6 x M20
Material (body)
Sheet steel enclosure
Environmental
Operating temperature
-10 to +60°C(EN54-20)
Relative humidity
0 to 90% noncondensing
Environment
Indoor
IP rating
IP40
Operating temperature -10ºC to +60ºC (EN54-20)
Relative humidity 0 to 90% RH (non condensing)
Regulatory
Certification
EN54-20
Supply
Voltage 21.6 to 26.4 Vdc
Current 450 mA at fan speed 8
Mechanical
Size 427mm (W) x 372mm (H) x 95mm (D)
Weight 5.2Kg
Colour Cream
Material Sheet steel enclosure
Cable entries 6 x M20
Sampling pipework
Inlets 4
Lenght 100m maximum single run (50m in moving air)
200m Combined maximum
Diameter 27mm OD
Holes up to 100 holes
Exhaust 1 (optional)
Inputs
Standard 3 - Progammable
Outputs
Standard 5 - Pre-Alarm, Alarm, Alarm2, Aux Alarm (n/o) and Fault (n/c)
Rating 500mA @ 30V
User interface
Indicators LED