FHSD8200-99
LaserSense HSSD2 High Sensitivity Smoke Detector
- High sensitivity provided by laser based forward light scatter for reliable early warning
- Combined sampling pipe up to 200m in length (still air)
- Unique ClassiFire® Perceptive Artificial Intelligence system that dynamically adjusts the detector’s operating parameters, allowing for day to day changes in the protected environment and dust separation system contamination
- Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and elimination system
- RS485 communications built in as standard for networking and remote communications
Related products
At a glance
Description
LaserSense HSSD2 is designed to provide very high sensitivity smoke detection, ensuring the very earliest warning of incipient fire with minimum rate of nuisance alarms.
ClassiFire Perceptive Artificial Intelligence ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.
Upgradable volt-free Fire and Fault relay outputs are available for remote monitoring by local fire detection or BMS systems.
ClassiFire Perceptive Artificial Intelligence ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.
Upgradable volt-free Fire and Fault relay outputs are available for remote monitoring by local fire detection or BMS systems.
Typical Applications
• Data storage units
• Prison cells
• Plant rooms
• Air conditioning units
• Equipment racks
• Computer rooms
• Air duct protection
• Heritage property protection
• Critical equipment
• Anti-smoking enforcement
• Motor rooms
• Prison cells
• Plant rooms
• Air conditioning units
• Equipment racks
• Computer rooms
• Air duct protection
• Heritage property protection
• Critical equipment
• Anti-smoking enforcement
• Motor rooms
Options Available
• Addressable Protocol Interface Cards APIC™ available for Ziton protocol
• Command Module available for central monitoring and display
• SenseNet compatible - up to 127 detectors per loop
• Remote Display units available
• Suitable for MatrixScan, a patented software system which provides virtual addressable location detection - e.g. 10 physical detectors would provide up to 45 unique addressable locations.
• Command Module available for central monitoring and display
• SenseNet compatible - up to 127 detectors per loop
• Remote Display units available
• Suitable for MatrixScan, a patented software system which provides virtual addressable location detection - e.g. 10 physical detectors would provide up to 45 unique addressable locations.
Details
- High sensitivity provided by laser based forward light scatter for reliable early warning
- Combined sampling pipe up to 200m in length (still air)
- Unique ClassiFire® Perceptive Artificial Intelligence system that dynamically adjusts the detector’s operating parameters, allowing for day to day changes in the protected environment and dust separation system contamination
- Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and elimination system
- RS485 communications built in as standard for networking and remote communications
Technical specifications
| General | ||
|---|---|---|
| Status indication |
LED and LCD
|
|
| User interface |
Keypad
|
|
| Alarm levels |
4 (Aux, Pre-alarm, Alarm and Alarm 2)
|
|
| Electrical | ||
|---|---|---|
| Operating voltage |
21.6 to 26.4 VDC
|
|
| Current consumption |
450 mA at fan speed 8
|
|
| Detection | ||
|---|---|---|
| Detection principle |
Laser light scattering mass detection and particle evaluation
|
|
| Range |
0.0015% to 25% (%Obs/m)
|
|
| Particle sensitivity range |
0.003μ to 10μ
|
|
| Sampling pipe | ||
|---|---|---|
| Length |
100 m maximum single run (50 m in moving air), 200 m Combined maximum
|
|
| Inlet quantity |
4
|
|
| Inlet size |
27 mm OD
|
|
| Exhaust |
1 (optional)
|
|
| Input | ||
|---|---|---|
| Input quantity |
3, Progammable
|
|
| Output | ||
|---|---|---|
| Output quantity |
5, Pre-Alarm, Alarm, Alarm2, Aux Alarm (n/o) and Fault (n/c)
|
|
| Output type and rating |
500 mA @ 30 V
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
427 x 372 x 95 mm (W x H x D)
|
|
| Net weight |
5.2 kg
|
|
| Colour |
Cream
|
|
| Mounting type |
Surface mount
|
|
| Cable entries |
6 x M20
|
|
| Material (body) |
Sheet steel enclosure
|
|
| Environmental | ||
|---|---|---|
| Operating temperature |
-10 to +60°C (EN54-20)
|
|
| Relative humidity |
0 to 90% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP40
|
|
| Regulatory | ||
|---|---|---|
| Certification |
EN54-20
FM
UL
|
|
| Sampling pipework | ||
|---|---|---|
| Holes | up to 100 holes | |
Downloads
All downloadsDatasheet
Technical documentation
CPD / CPR
Certificates
DoP
KGS F&S - DoP_360-3514-0199_Stratos HSSD2, LaserSense HSSD2
DoC
KGS F&S - DoC_10-3514-356-0199_HSSD2
Other EU certificate
Other EU certificate
VMC_G203024_Stratos HSSD2
Other EU certificate
VMC_PR-1751/064_ZP-2 (2010-2 series)
Other EU certificate
VMC_PR-1724/064_ZP2
Other EU certificate
VMC_PR-1723/064_KFP-A
Other EU certificate
VMC_PR-1720/064_2X
Other EU certificate
VMC_PR-1719/064_2X
Other EU certificate
VMC_APF-1360_2X
Other EU certificate
VMC_APF-1326_ZP2
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.