ZR432-2P
Ziton series optical/heat detector with ZR401-3P wireless base & battery pack, polar white
- No external aerials improves aesthetics
- Dual battery supply with up to 5 year battery life
- Full status monitoring – batteries, head supervision and tamper
- Multifunctional, configurable for smoke only, heat ony of both smoke and heat
- 2-way wireless communication with variable power output
Related products
At a glance
General
The ZR432-2P is a wireless, POLAR WHITE addressable multisensor capable of operating in optical, heat or multisensor (optical/heat) modes.
Fast response to a wide range of fires
Designed to provide the earliest response to a wide range of fire types in locations where hard wiring is not an option, ZR432-2 detectors combine optical smoke sensing and thermal monitoring to provide an accurate warning of fire. Smoke sensing may be isolated for areas where ambient smoke may exist at certain times of the day, or used on a day night basis in premises where heat only is required whilst the building is occupied.
Detector control
The ZR432-2 detector is controlled from the main control panel via a loop wired radio interface module allowing both wireless and hardwired devices to be seamlessly located and controlled from the same wiring loop. Every wireless device controlled through the radio loop module, is assigned its own IDENT address with which the main control panel communicates, providing the same system facilities as directly wired devices.
System operation
Temperature and smoke sensitivity may be set by a selection of switches located in the base of the ZR432-2. Calibration and self-testing are carried out automatically.
Removal or replacement of an incorrect sensing devices are identified by the system and details displayed at the main control panel. Sophisticated auto contamination adjustment compensates for any long-term drift in performance caused by dirt entering the sensing chamber.
For ease of removal, ZR432-2 detectors plug into the radio base by a simple twist and lock action.
Removal or replacement of an incorrect sensing devices are identified by the system and details displayed at the main control panel. Sophisticated auto contamination adjustment compensates for any long-term drift in performance caused by dirt entering the sensing chamber.
For ease of removal, ZR432-2 detectors plug into the radio base by a simple twist and lock action.
Details
- No external aerials improves aesthetics
- Dual battery supply with up to 5 year battery life
- Full status monitoring – batteries, head supervision and tamper
- Multifunctional, configurable for smoke only, heat ony of both smoke and heat
- 2-way wireless communication with variable power output
- Configurable sensitivity setting
- ETSI 300-220 approved
Technical specifications
| General | ||
|---|---|---|
| Status indication |
Red alarm LED
|
|
| Wireless frequency |
868 MHz
|
|
| Compatibility |
Ziton wireless systems
|
|
| Connectivity |
Wireless 868 MHz
|
|
| Addressing method |
Electronic
Unique address embedded
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
Batteries
|
|
| Batteries |
3 x AA (MN1500 LR6) Duracell alkaline batteries
3 x C (MN1400 LR14) Duracell alkaline batteries
|
|
| Operating voltage |
3 VDC
|
|
| Output transmitter power |
0 to 14 dBm
|
|
| Detection | ||
|---|---|---|
| Detection principle |
Smoke element - Photoelectric light scatter, Heat element - Thermistor
|
|
| Monitoring |
Continuously self-checking
|
|
| Sensitivity |
Configurable
|
|
| Coverage area |
Smoke element <100 m², Heat element < 50 m², Subject to local regulations
|
|
| Alarm temperature (maximum) |
+70°C
|
|
| Alarm temperature (minimum) |
+54°C
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
106 x 75 mm (including base) (Ø x H)
|
|
| Net weight |
350 g (including base & batteries)
|
|
| Colour |
Polar white
|
|
| Mounting type |
Base mount
Surface mount
|
|
| Material (body) |
Moulded ABS
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10 to +55°C
|
|
| Storage temperature |
-20 to +70°C
|
|
| Application temperature (maximum) |
+50°C
|
|
| Application temperature (typical) |
+25°C
|
|
| Relative humidity |
10 to 95% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP32
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 3
WEEE
|
|
| Certification |
CPR
|
|
| Standards |
EN54:5, EN54:7, EN54:25, ETSI 300-220
|
|
Downloads
All downloadsDatasheet
Certificates
CE
DoC - EC Declaration of Conformity
DoP
DoP 0359-CPR-0128
Non EU certificate
VMC_UAE_APF-1324_ZR432
DoC
KGS F&S - DoC_10-4213-356-0199_ZX432-2P
DoP
KGS F&S - DoP_360-4213-0199_ZX432
Non EU certificate
ICASA - TA-2025/3237
CPD / CPR
CPD / CPR
Certificate of Constancy of Performance (EN54-3, EN54-25)
CPD / CPR
Certificate of Constancy of Performance (EN54-25)
CPD / CPR
CPR_0370-CPR-1818_ZX432-2P
Other EU certificate
Installation sheet
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.