Skip to main content

2X-AFR-S

Addressable fire panel repeater, small cabinet
  • Local or global repeater with or without global control functionality
  • Up to 24 LED Zone indicators for Fire and Fault with space for a 4 digit number
  • Auto configuration, setup wizards and default regional setup modes
  • Ethernet port with TCP/IP for remote diagnostics, maintenance and programming
  • EN54 compliant graphical LCD with icons and up to 256 zones
View all

Related products

At a glance

Overview

The new 2X-A series life safety control systems bring the speed and functionality of high-end intelligent processing to small to mid-sized addressable applications. Based on 2X series learned experience and with complete backwards compatibility, the new 2X-A features an attractive contemporary design that fits with any decor. With improved robustness, manufactured in metal, special plastics and easy electronics removal, it allows painting in any colour. The main controls are easily located using an improved and robust jog dial.
With high power loop addressable detection, a full line of easily configured option cards and modules, as well as USB and Ethernet® connectivity, these quick-to configure systems offer versatility that benefits building owners and life safety system installers alike.

The Panel

The fire panel repeaters supplied in local language come with a 2010-2A-NB network board already fitted. Except for having no addressable loops and corresponding programmable outputs, the setup is similar as a normal fire panel. It and has its own power supply, 2 conventional relay outputs and 2 supervised outputs, working in pair and dedicated to common fire and fault conditions, as well as 2 user configurable inputs for monitoring and control are available.

Options

The repeaters use a node on the network, similar like a normal panel with a maximum of 32 nodes / 32 loops network of fire panels and fire panel repeaters (including conventional fire panels and fire panel repeaters up to a maximum of 64 conventional zones). Last but not least, in case seperate zone indications are required, a 20 or 40 zone fire/fault LED indicator board can be mounted in the panel or repeater with ample space for text.
Network compatible with existing panels, repeaters (existing and new) and conventional panels.

Approvals & compliance

• CE / CPD / EN54-2 / EN54-4 / EN54-21
• WEEE / RoHS compliant

Details

  • Local or global repeater with or without global control functionality
  • Up to 24 LED Zone indicators for Fire and Fault with space for a 4 digit number
  • Auto configuration, setup wizards and default regional setup modes
  • Ethernet port with TCP/IP for remote diagnostics, maintenance and programming
  • EN54 compliant graphical LCD with icons and up to 256 zones
  • Improved Jog Dial with 4 soft buttons for simple and intuitive user control
  • Aesthetic pleasing design with robust painted steel door
  • Easy removable door and chassis for quick and clean installation
  • All pluggable connectors
  • Up to 72 hours standby time and 30 minutes alarm
  • 3 USB ports with memory stick support and RS232 for printer support
  • 3 operator level menu structure (20 usernames and passwords)
  • Email notification for events directly from the panel (4 user accounts)
  • History log memory for 9999 events
  • Backwards compatible, supporting site retrofit/upgrades, expansions, replacement
  • Comes standard fitted with network board

Technical specifications

General
User interface
Without fire Brigade controls
Network size (nodes)
up to 64
Electrical
Power supply type
VAC
Operating voltage
110 / 240 VAC (+10%/-15%), 50 / 60 Hz (±5%)
Mains supply cable type: 3 x 1.5 mm² (live, neutral, earth)
Current consumption
Nom. 0.6 / 1.3 A, Max. 1.5 A / 3.15 A
Fuse rating: 2 / 4 A
Input
Input quantity
2
Input type and rating
150 mA (max. Load), Cable type: Recommended 2 core 1.5 mm² twisted pair
Programmable
2
Termination
15 kohm
Output
Output type and rating
Cable type: Recommended 2 core 1.5 mm² twisted pair
Auxilliary power
1 resetable, 500 mA, 19.5 to 28 VDC (24 VDC nominal)
Termination
15 kohm
Standby battery
Capacity
Max. 2 x 12 V / 18 Ah
Charging
27.3 V at 20ºC ; 36 mV/ºC
Low battery warning threshold
23.6 VDC ± 1% at 25ºC
Batteries supported in housing
Max. 2 x 12 V / 7.2 Ah
Physical
Form factor
Large
Physical dimensions
446 x 536 x 164 mm (W x H x D)
Net weight
7.4 kg (without battery)
Shipping weight
10.1 kg
Colour
White (RAL 9003)
Mounting type
Surface mount
Cable entries
18 (20 mm) / 2 (20 mm) / 2 removable plates (top / bottom / back)
Material
Steel (painted)
Environmental
Operating temperature
-5 to +40°C
Storage temperature
-20 to +50°C
Relative humidity
10 to 95% noncondensing
Environment
Indoor
IP rating
IP30, indoor use only
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
BOSEC
CE