TCC-0007
IS sounder/beacon, 24 V, amber lens
- Approved by ATEX, IECEx
- Group I MI Ex ia I Ma
- Group II IGD Ex ia IIC T6 Ga, Ex ia IIIC T85˚C Da
- Zones 0, 1, 2, 20, 21 & 22
- Conforms to: EN 60079-0:2012 + All:2013 (IEC 60079-0:2011) EN-60079-11:2012 + (IEC 60079-11:2011)
Related products
At a glance
IS Sonos sounder beacon
The IS Sonos sounder beacon has been approved for use in potentially explosive atmospheres for Group I (Mining) & Group II (Above Ground) applications and incorporates a high Ingress Protected IP66 enclosure.
The sounder beacon unit incorporates a two stage alarm option and has a total of 32 selectable tones, selectable via a dip switch on the PCB and produces up to 105 dB at 1 meter. A specially designed time saver base enables quick and easy installation of this unit with no extra cabling to be made to the head of the unit.
Connections are made to the base during the initial wiring phase which results in a faster more reliable installation. The sounder head simply twists & clicks into the pre-fixed base on commissioning avoiding any additional wiring & connections.
Further details can be found on the installation sheet’ This unit must be used in conjunction with an approved Zener Barrier or Galvanic Isolator. The characteristics should not exceed Uo: 28 V, Io: 93 mA, Po: 660 mW, Ci: 0, Li 0. The minimum value of Uo should not drop below 23.6 V and the minimum value of Io should not drop below 50 mA.
The sounder beacon unit incorporates a two stage alarm option and has a total of 32 selectable tones, selectable via a dip switch on the PCB and produces up to 105 dB at 1 meter. A specially designed time saver base enables quick and easy installation of this unit with no extra cabling to be made to the head of the unit.
Connections are made to the base during the initial wiring phase which results in a faster more reliable installation. The sounder head simply twists & clicks into the pre-fixed base on commissioning avoiding any additional wiring & connections.
Further details can be found on the installation sheet’ This unit must be used in conjunction with an approved Zener Barrier or Galvanic Isolator. The characteristics should not exceed Uo: 28 V, Io: 93 mA, Po: 660 mW, Ci: 0, Li 0. The minimum value of Uo should not drop below 23.6 V and the minimum value of Io should not drop below 50 mA.
Application
Fire, Security, Process Control and general signalling applications.
Details
- Approved by ATEX, IECEx
- Group I MI Ex ia I Ma
- Group II IGD Ex ia IIC T6 Ga, Ex ia IIIC T85˚C Da
- Zones 0, 1, 2, 20, 21 & 22
- Conforms to: EN 60079-0:2012 + All:2013 (IEC 60079-0:2011) EN-60079-11:2012 + (IEC 60079-11:2011)
- Diode Polarised and End of Line resistor compatible
- Dustproof and weatherproof
Technical specifications
| General | ||
|---|---|---|
| Compatibility |
TCC-0012, GBX370
|
|
| System support |
Conventional intrinsically safe systems
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
24 VDC
|
|
| Operating voltage |
24 VDC
|
|
| Current consumption |
33 mA
|
|
| Sounder | ||
|---|---|---|
| Output level |
>105 dB(A)
|
|
| Selectable tones |
32
|
|
| No. of stages |
2
|
|
| VID | ||
|---|---|---|
| Colour |
Amber
|
|
| Flash frequency |
1 Hz or constant (ON)
|
|
| Physical | ||
|---|---|---|
| Net weight |
0.33 kg
|
|
| Colour |
Red
|
|
| Mounting type |
Base mount
|
|
| Mounting position |
Ceiling
Wall
|
|
| Mounting base |
Deep
|
|
| Material |
Flame retardant Polycarbonate
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-40 to +55ºC
|
|
| Relative humidity |
>90% at 20ºC
|
|
| Hazardous environment rating |
Intrinsically safe - Zones 0, 1, 2, 20, 21 & 22
|
|
| IP rating |
IP66
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 3
WEEE
|
|
| Certification |
CENELEC/ATEX
CPR
|
|
| Standards |
ATEX (EMT17ATEX0012X) IECEx (EMT 17.0005X)
EN54-3
|
|
Downloads
All downloadsOther EU certificate
CPD / CPR
Certificates
DoP
DoC
DoC
.Others - DoC_20-8206-356-0004_TCC-00xx
DoP
.Others - UKCA / CE Declaration of Performance
Datasheet
User manual
Application note
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.