Skip to main content

DC-9204E

Innovation Conventional Manual Call Point
  • Easy to install with plugin connector
  • Simple alarming activation
  • Easy reset using a special key
  • Protection hinged cover & outdoor mounting box available
  • Approved to the latest standards, LPCB marked
View all

Related products

At a glance

General

The DC-9204E is a conventional manual call point for use on compatible conventional systems. It allows user interaction with the fire alarm system for manual alarm reporting.

Operation

An alarm is reported by pressing the resettable element. The alarm is confirmed by the DC-9204E by an illuminated LED. The alarm is signalled automatically to the conventional fire alarm zone. To reset a special key is supplied with the unit.

Installation

The DC-9204E is simply connected by two wires to any compatible fire alarm zone monitor where it gets its power and reports events using the same 2 wires. The provided reset key is also used to unlock the MCP.
The DC-9204E is suitable for public places where accidental activation can be avoided by using an optional protection flip cover (D-92FC). For outdoor applications a weatherproof enclosure (D-92WPB) is additionally available.

Details

  • Easy to install with plugin connector
  • Simple alarming activation
  • Easy reset using a special key
  • Protection hinged cover & outdoor mounting box available
  • Approved to the latest standards, LPCB marked

Technical specifications

General
Status indication
Red LED
Compatibility
Most conventional zone monitors
Connectivity
Zone interface
Electrical
Power consumption
100 mW (max.)
Operating voltage
12 to 28 VDC
24 VDC (nominal)
Current consumption
0 mA (Standby)
≤30 mA (Alarm)
Cable specification
>1.0 mm²
No. of cable cores
2
Terminals
4
Detection
Detection principle
Microswitch
Coverage area
Subject to local codes
Zone length
CIE Specific
Isolation
Series resistance
470 Ω ½ W
Physical
Physical dimensions
87.1 x 87.1 x 58 mm (W x H x D)
Shipping weight
160 g
Colour
Red
Mounting type
Wall mount
Material (body)
ABS
Functional marking
House of Fire
Environmental
Vandal proof
No
Operating temperature
-10 to +50°C
Relative humidity
≤95% noncondensing
Environment
Indoor
IP rating
IP43
Regulatory
Compliancy
CE
Certification
CPR
Standards
EN54-11