ADELCU-EOL
Alarmline II Digital EN, Ersatz-Endwiderstand
- Simulieren Sie schnell einen Störungszustand
- Simulieren Sie schnell einen Alarmzustand
- Lieferung mit 2 IP67-zertifizierten Kabelverschraubungen
- Sicheres, wetterfestes Gehäuse
- RoHS-konform, CE- und EN54-28:2016-zertifiziert
Verwandte Produkte
Auf einen Blick
General
Replacement end-of-line unit for use with the AlarmLine II Digital EN linear heat detection controller and AlarmLine II Digital EN linear heat detection cable.
Functional testing
Internally the unit features 4 switches, which can be used to simulate a fire or fault on each of the zones. There are two push-buttons, one for each zone, which simulate a fire by connecting the two cable cores when the button is pressed. Similarly there are two switches, which under normal conditions connect the end-of-line resistor across the cable, for each zone. However when the switch is changed, this create an open circuit which in turn raises a fault on the controller. Via these switches it is easy to functionally test the system.
Einzelheiten
- Simulieren Sie schnell einen Störungszustand
- Simulieren Sie schnell einen Alarmzustand
- Lieferung mit 2 IP67-zertifizierten Kabelverschraubungen
- Sicheres, wetterfestes Gehäuse
- RoHS-konform, CE- und EN54-28:2016-zertifiziert
Technische Spezifikationen
| Electrical | ||
|---|---|---|
| Terminals |
5 mm rising clamp
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
94 x 94 x 57 mm (W x H x D)
|
|
| Environmental | ||
|---|---|---|
| Operating temperature |
-35 to +55°C
|
|
| IP rating |
IP66
|
|
| Regulatory | ||
|---|---|---|
| Certification |
CE
EN54-28
|
|
Herunterladen
All downloadsDatenblatt
Zertifikate
DoC
DoC_20-8201-356-0004_Thermocable_AlarmLine II
DoP
.Others - Declaration of Performance
RoHS
.Others - Manufacturers Declaration of Conformity